Inspection Detail
Inspection: 309769453 - Dubak Electrical Maintenance Corp.
Inspection Information - Office: Naperville Area Office
Site Address:
Dubak Electrical Maintenance Corp.
5 South 220 Frontenac Rd.
Naperville, IL 60563
Mailing Address:
417 South Bluff Ave., Lagrange, IL 60525
Union Status: NonUnion
SIC:1731
NAICS: 238210/Electrical Contractors
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 03/15/2007
Planning Guide: Safety-Construction
Emphasis: S:Electrical
Case Closed: 03/15/2007
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 100821669 |
Investigation Summary
On November 13, 2006, Employee #1 received a call on his cell phone from a coworker asking him to find the serial/order number of a 480-volt/three-phase attachment plug so that more attachment plugs could be ordered. Employee #1 found such a plug, possibly choosing it because it was in an idle machine and the only one not in production. Employee #1 accidentally placed the ground prong into the energized plug receptacle and grounded out, causing the third-phase fuse to blow. He was electrocuted. The wiring and the Chicago Pyle/National attachment plug were found to be very dilapidated and had not been inspected or maintained. Because of the configuration of the plug, any of the eight-prong male plugs could have been inadvertently placed in any of the female receptacles, energizing the metal casing. Because of Employee #1's medical condition and the fact that there were no electrical burns inside or outside his body, the coroner considered ruling the cause of death as natural causes/coronary disease. After continuity testing and destructive testing of the evidence, the cause of death was ruled to be electrocution.
Keywords: FUSE, ELECTRICAL, INADEQUATE MAINT, WORK RULES, ELECTROCUTED, CONSTRUCTION, ELECTRICAL WORK, ATTACHMENT PLUG, ELEC CIRC PART--MISC
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 309769453 | Fatality | Electric Shock | Electricians |
Translate