Inspection Detail
Inspection: 301951117 - Grand Cove Marina Inc.
Inspection Information - Office: Hasbrouck Heights Area Office
Site Address:
Grand Cove Marina Inc.
989 River Road
Edgewater, NJ 07023
Mailing Address:
523 River Road, Edgewater, NJ 07020
Union Status: NonUnion
SIC:4493
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 08/12/1998
Emphasis:
Case Closed: 08/26/1998
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 101380160 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 4 | 4 | ||||
| Current Violations | 4 | 4 | ||||
| Initial Penalty | $3,750 | $0 | $0 | $0 | $0 | $3,750 |
| Current Penalty | $3,750 | $0 | $0 | $0 | $0 | $3,750 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 19100303 G02 I | 08/12/1998 | 08/17/1998 | $750 | $750 | $0 | - | ||
| 2. | 01002A | Serious | 19100304 A02 | 08/12/1998 | 08/17/1998 | $1,500 | $1,500 | $0 | - | ||
| 3. | 01002B | Serious | 19100304 A03 | 08/12/1998 | 08/17/1998 | $0 | $0 | $0 | - | ||
| 4. | 01003 | Serious | 19100304 E01 I | 08/12/1998 | 08/17/1998 | $750 | $750 | $0 | - | ||
| 5. | 01004 | Serious | 19100304 F04 | 08/12/1998 | 08/17/1998 | $750 | $750 | $0 | - |
Investigation Summary
An employee for a marina was using a Simer Geyser Submersible Utility Pump to pump out the bilge of a work barge. The pump was equipped with float switch and was connected via an extension cord to a dockside 125-volt receptacle outlet. The receptacle was improperly wired with the line and neutral connections reversed. Also, the cord set had been repaired and the receptacle cord cap was missing the equipment grounding prong. The employee was electrocuted when he stepped into the water-filled bilge of the barge and contacted a grounded surface. (The employee also had second-degree electrical burns on his back and above his right eye.)
Keywords: RECEPTACLE, ELECTRICAL, REVERSE POLARITY, CORD SET, E GI VII, ELECTROCUTED, GROUND FAULT, EQUIPMENT GROUNDING, PUMP
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 301951117 | Fatality | Electric Shock | Occupation not reported |