Violation Detail
Standard Cited: 19100134 I05 IV Respiratory Protection.
Inspection Nr: 1806145.015
Citation: 02001
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 06/12/2025
Nr Instances: 1
Nr Exposed: 6
Abatement Date: 07/10/2025
Gravity:
Report ID: 0729700
Contest Date:
Final Order: 07/01/2025
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 07/01/2025 | $0.00 | 07/10/2025 | Other | |
| Penalty | Z: Issued | 06/12/2025 | $0.00 | 07/10/2025 | Other |
Text For Citation: 02 Item/Group: 001 Hazard:
29 CFR 1910.134(i)(5)(iv):The tag containing the most recent change to the sorbent beds was not maintained at the compressor: Compressor used for breathing airline system did not have a tag showing most recent change date of the sorbent beds and the signature of the person authorized by the employer to perform the change at the following instances: 1) Sullair LS-20S located at Plant III 2) Sullair DSP-75AT6N-M125 (AC-1) Maintenance No. 303080 located at Building 46 3) Sullair DSP-75AT6N-M125 (AC-2) Maintenance No. 303081 located at Building 46 4) Sullair V130 DS Maintenance No. 10048198 located at Plant IV 5) KAISHAN Krof 200 Maintenance No. 46898 located at Plant IV 6) Sullair Maintenance No. 300420 located at Plant I 7) Sullair V-320TS Maintenance No. 10046440 located at Plant I 8) Sullair Maintenance No. 301431 located at Plant I