Violation Detail
Standard Cited: 19100303 G02 I General.
Inspection Nr: 1401131.015
Citation: 01016
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $13,260.00
Current Penalty: $7,956.00
Issuance Date: 11/13/2019
Nr Instances: 4
Nr Exposed: 13
Abatement Date: 11/25/2019
Gravity: 10
Report ID: 0215800
Contest Date: 11/21/2019
Final Order: 10/14/2021
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | F: Formal Settlement | 10/14/2021 | $7,956.00 | 11/25/2019 | Serious | |
| Penalty | C: Contested | 11/22/2019 | $13,260.00 | 11/25/2019 | Serious | |
| Penalty | Z: Issued | 11/13/2019 | $13,260.00 | 11/25/2019 | Serious |
Text For Citation: 01 Item/Group: 016 Hazard:
29 CFR 1910.303(g)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by approved cabinets or other forms of approved enclosures, or other means listed under this provision: a) Foundry MCC Room, on or about 5/15/19: Air compressor #2 electrical cabinet, 460-volts, had exposed live parts in that the cabinet doors were kept open to allow heat to escape. b) Foundry MCC Room, on or about 5/15/19: Sprue dust collector electrical cabinet, 460-volts, had exposed live parts in that the cabinet doors were kept open to allow heat to escape. c) E-Melt Basement, on or about 9/06/19: Capacitor bank, 480-volts, approximately 7-feet above the floor, was not equipped with an approved enclosure to guard against accidental contact with live parts. d) Foundry Office, on or about 9/6/19: Light fixture 7-feet 6-inches above the floor had live conductors that were not guarded against accidental contact.