Violation Detail
Standard Cited: 19100253 B04 Oxygen-fuel gas welding and cutting.
Inspection Nr: 1401131.015
Citation: 01008B
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 11/13/2019
Nr Instances: 1
Nr Exposed: 11
Abatement Date:
Gravity: 5
Report ID: 0215800
Contest Date: 11/21/2019
Final Order: 10/14/2021
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | F: Formal Settlement | 10/14/2021 | $0.00 | Serious | ||
| Penalty | C: Contested | 11/22/2019 | $0.00 | Serious | ||
| Penalty | Z: Issued | 11/13/2019 | $0.00 | Serious |
Text For Citation: 01 Item/Group: 008B Hazard:
29 CFR 1910.253(b)(4): Oxygen cylinders in storage were not separated from fuel gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one half hour: a) Welding Area, on or about 5/13/19: Oxygen and acetylene compressed gas cylinders were stored together within 5 feet of each other and were not separated by a noncombustible barrier at least 5 feet high having a fire-resistance rating of at least one half hour.
Translate