Violation Detail
Standard Cited: 19100119 D03 I B Process safety management of highly hazardous chemicals.
Inspection Nr: 446413.015
Citation: 01002
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $4,675.00
Current Penalty: $4,675.00
Issuance Date: 11/13/2012
Nr Instances: 4
Nr Exposed: 1100
Abatement Date: 11/13/2013
Gravity:
Report ID: 0728900
Contest Date: 11/29/2012
Final Order: 12/20/2013
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | F: Formal Settlement | 12/20/2013 | $4,675.00 | 11/13/2013 | Other | |
| Penalty | C: Contested | 12/05/2012 | $4,675.00 | 02/14/2013 | Serious | |
| Penalty | Z: Issued | 11/13/2012 | $4,675.00 | 02/14/2013 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1910.119(d)(3)(i)(B): The employer did not include all equipment that was part of the process on piping and instrument diagrams. Piping and instrument diagrams (P & IDs) for the facility ammonia refrigeration system were not updated to reflect all system components including, but not limited to: A) Gauges added to new lines for Vilter compressors #1, #2, and #7 in the compressor room. B) Valves #030138 and #030137 in lines for the 40 degree Suction Trap were not located in the positions indicated by the relevent P&ID.