Violation Detail
Standard Cited: 19100134 I05 I Respiratory Protection.
Inspection Nr: 1799884.015
Citation: 01002
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $8,511.00
Current Penalty: $5,957.70
Issuance Date: 04/04/2025
Nr Instances: 1
Nr Exposed: 2
Abatement Date:
Gravity: 5
Report ID: 0729700
Contest Date:
Final Order: 04/24/2025
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 04/24/2025 | $5,957.70 | Serious | ||
| Penalty | Z: Issued | 04/04/2025 | $8,511.00 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1910.134(i)(5)(i): Compressors used to supply breathing air to respirators were not so constructed and situated so as to prevent entry of contaminated air into the air-supply system: Employees are exposed to respiratory health hazards. At the Southwest area of the building, the intake of the Sullair Industrial Air Compressor model no. 12BS-50H ACAC is located at the employee's parking lot, where vehicles back up next to the intake system and toxic exhaust gases could be pulled into the compressed air system and supplied air system.