Violation Detail
Standard Cited: 19100119 H03 IV Process safety management of highly hazardous chemicals.
Inspection Nr: 1781440.015
Citation: 01002
Citation Type: Serious
Abatement Status:
Initial Penalty: $16,550.00
Current Penalty: $16,550.00
Issuance Date: 04/10/2025
Nr Instances: 5
Nr Exposed: 7
Abatement Date: 05/22/2025
Gravity: 10
Report ID: 0626700
Contest Date: 05/02/2025
Final Order:
Related Event Code (REC): A
Emphasis:
Substance: 1480
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | C: Contested | 05/08/2025 | $16,550.00 | 05/22/2025 | Serious | |
| Penalty | Z: Issued | 04/10/2025 | $16,550.00 | 05/22/2025 | Serious |
Text For Citation: 01 Item/Group: 002 Hazard:
29 CFR 1910.119(h)(3)(iv): The contract employer did not assure each contract worker follows safe work practices of the facility. On or about October 10, 2024, in ARU #6/7 at Deer Park Refinery Limited located in Deer Park, TX, the contract employer (Repcon, Inc.) did not ensure that its workers follow the required host employer safe work practices including but not limited to: a) Repcon supervisors and employees did not sign in on the unit entry log before entering the process unit and they did not sign out upon leaving. b) Repcon supervisors did not discuss the identified hazards and control measures with all craftworkers working on the permits (#410545, #411121 and #411125) in their Job Safety Analyses (JSAs). c) Repcon supervisors did not follow the instructions in the work permit# 411125 and failed to ensure the unit operator was present for line break work for the CAG header and flare line. d) Repcon supervisors did not complete the written contingency plan with the unit operator before accepting the work permit# 411125. e) Repcon supervisors did not ensure that all crew members sign on Master isolation Sheet and review the contingency plan and isolation points.
Translate