Violation Detail
Standard Cited: 19260416 A01 General requirements.
Inspection Nr: 1491715.015
Citation: 01001
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $13,494.00
Current Penalty: $13,494.00
Issuance Date: 11/13/2020
Nr Instances: 1
Nr Exposed: 1
Abatement Date: 11/30/2020
Gravity: 10
Report ID: 0521400
Contest Date:
Final Order: 12/11/2020
Related Event Code (REC): A
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | Z: Issued | 11/13/2020 | $13,494.00 | 11/30/2020 | Serious |
Text For Citation: 01 Item/Group: 001 Hazard:
29 CFR 1926.416(a)(1): Employees were permitted to work in proximity to electric power circuits and were not protected against electric shock by de-energizing and grounding the circuits or effectively guarding the circuits by insulation or other means: On or about September 4, 2020, an employee was electrocuted while terminating electrical conductors inside an energized 480/277 volt switchgear distribution cabinet. Energized circuits inside the distribution cabinet were not de-energizing and grounded or effectively guarded, exposing the employee to the hazards associated with electrical shock- electrocution. Abatement documentation is required of this item in accordance with the requirements of 29 CFR 1903.19(d).