Accident Report Detail
Accident Summary Nr: 170606891 - Employee exposed to ethylene oxide
| Inspection Nr | Date Opened | SIC | NAICS | Establishment Name |
|---|---|---|---|---|
| 119843720 | 02/14/1994 | 8062 | 0 | Century City Hospital |
Abstract: On the afternoon of January 20, 1994, an ethylene oxide leak occurred on the p-1 level of Century City Hospital in the Central Services area. This occurred during the sterilization cycle on the ethylene oxide gas sterilizer (AMSCO model #2027). During the cycle, the equipment emitted a pulsing audible buzzer, signifying a mechanical failure. Employee #1 mistook the sterilizer pulsing buzzer for a solid buzzer that signals the completion of the sterilization cycle. When he opened the sterilizer door to transfer the load to a secondary aerator for a second sterilization cycle, ethylene oxide was released into the immediate area, exposing Employee #1 and sending a high alarm reading on the ethylene oxide monitor. A serious accident related citation was issued (5220(j)(3)(c)(3)).
| Employee # | Inspection Nr | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 119843720 | Non Hospitalized injury | Cancer | Health technologists and technicians, n.e.c. |