Accident Report Detail
Accident Summary Nr: 147964.015 - Employee Dies After Being Electrocuted Due to Damaged Cable
| Inspection Nr | Date Opened | SIC | NAICS | Establishment Name |
|---|---|---|---|---|
| 1608626.015 | 07/18/2022 | 332312 | Rack Builders, Inc. |
Abstract: At 1:50 a.m. on July 16, 2022, an employee was closing an overhead door adjacent to a welding station at a fabricated metal manufacturing facility. A portable electric fan mounted on a pedestal was plugged into a wall receptacle at the overhead door. Coworkers noticed several minutes later than the employee was sitting on a crate at the overhead door and his left arm was in contact with the portable fan. When a coworker attempted to close the overhead door and moved the portable electric fan, he noticed an electric arc when contact between the fan and the employee's arm was broken. A coworker initiated CPR and requested medical assistance. The employee was transported to the local hospital where he died from the electric shock injuries. It was determined that the portable cord run through a wire way hole was exposed to a sharp edge which cut the wire sheath and insultation and exposed the bare conductor. The attachment plug was also missing the ground pin.
| Employee # | Inspection Nr | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 1608626.015 | 32 | M | Fatality | Welders and cutters |
Translate