Accident Report Detail
Accident Summary Nr: 118464.015 - Employee incurs shock and burns from energized bushing
| Inspection Nr | Date Opened | SIC | NAICS | Establishment Name |
|---|---|---|---|---|
| 1419422.015 | 07/31/2019 | 221122 | Ameren Illinois |
Abstract: At 12:45 p.m. on July 29, 2019, an employee was preparing to remove an electrical lead from a bushing on a portable substation. The employer had added a maintenance breaker which allowed maintenance personnel to supply power to a motor that moved a tap changer. The maintenance breaker allowed an extension cord, used to maintain batteries and supply power to a heater, to back-feed electricity through the transformers and up to the bushing that the employee was touching. The maintenance breaker was not operated in a manner to control the energy to the equipment. The employee incurred an electrical shock and burns to his back and hands which required hospitalization.
| Employee # | Inspection Nr | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 1419422.015 | 38 | M | Hospitalized injury | Electrical power installers and repairers |
Translate